What inspections are required for my Building Permit?*
Footing - Prior to placement of concrete, after all forms, reinforcement, stanchions, piers or trenches are in place.
Foundation Reinforcement - Prior to placement of concrete, after wall forms are installed any required reinforcement must be securely tied in place.
Subsoil - For house and attached garage, prior to placement of concrete floor, after trade undergrounds are inspected and approved, if applicable. Floor base and vapor retarder must be installed. Also, walkout basement slab insulation. Appendix F - Radon Control Methods are also required.
Masonry - Inspection prior the installation of masonry veneer and after the installation of base course flashing and weather-resistant sheathing paper as specified and after completion of masonry construction to verify weep holes and flashing as required.
Rough Framing - Prior to concealing any framing, after Electrical, Mechanical, Plumbing rough inspections have been approved.**
Insulation - After all exterior wall insulation is installed but prior to dry walling or other wall surface covering.
Fire-Resistance-Rated Construction - When fire-resistance-rated construction is required between dwelling units after: lathing/ wallboard is in place, prior to covering joints and fasteners with plaster, or taped and finished.
Fireplace - (Masonry) - When the damper and first flue liner are in place. Optional inspection.
Final - After Electrical, Mechanical, Plumbing final inspections have been approved. Before building is occupied.
What are common violations noted during building
inspections?
"Graspable" handrail required three or more risers.
Concentrated point loads missing solid bearing to foundation.
Firestopping of intersections of floor/ceiling, soffits, columns, mechanical chases.
Roof and Floor Engineering (truss drawings, I- Joists) required for rough inspection, bracing, damaged or altered, proper fastening of girders.
Improper or missing installation of mechanical connectors (hangers, angles, straps etc.)
Foundation anchorage - Minimum 2 per plate, Maximum 12" from ends/breaks in plates, spacing to manufacturers' specifications.
Stair geometry inconsistency - 3/8" maximum variance between risers, 8 1/4" maximum riser.
Improper final grading, minumum 1" per foot - to a distance of 8' away from house.
Exterior caulking and sealing.
Safety glazing - within 24" of doors, in tub/shower enclosures, within 18" of floor and greater than 9 square feet of area.